A micro inverter is a small inverter that converts the DC power of one, two or four solar panels, depending on the model, into grid-compatible AC at the panel itself. Its output is DC power times inverter efficiency, so a 400 W panel at the 96 percent PVWatts default delivers about 384 W AC before other system losses.
A quote arrives with one small box behind every panel, where the last quote showed one large inverter on the garage wall. The first question buyers ask is what is a micro inverter, and whether the extra boxes change the energy a roof delivers. This guide defines the device, runs the arithmetic on a 400 W panel, shows how much a micro inverter for solar can recover, and lists the datasheet numbers to check before ordering.

What is a micro inverter
A micro inverter is a small inverter that converts the DC output of one, two or four solar panels, depending on the model, into AC at the panel itself. The unit mounts under or beside its panel and tracks the maximum power point of that panel alone, which means it adjusts the electrical load on the panel to extract the most power under the light it receives at that moment.
The AC outputs of all units join on a shared branch circuit, and that circuit runs to the grid connection point. The roof therefore carries panel-level DC only between each panel and its own unit, while everything beyond the unit is AC wiring.
A string inverter performs the same conversion once for a whole series string of panels. The two layouts differ in where the conversion happens, and that placement decides how shading, panel mismatch and monitoring behave.
The governing relation is daily AC energy in watt-hours equals panel watts times peak sun hours times one minus the system loss fraction times inverter efficiency. Peak sun hours are the daily solar energy on the panel plane in kWh/m2/day, which numerically equals the hours at 1,000 W/m2 that would deliver the same energy. This simplified formula borrows two PVWatts defaults, a 14 percent total system loss and a 96 percent inverter efficiency, and the next section uses both.
For the single-unit basics behind this conversion, the guide on what is an inverter covers the DC to AC step, and inverter vs converter separates it from DC to DC conversion.
Worked example, step by step
One micro inverter behind a 400 W panel delivers about 1,651 Wh of AC energy per day at 5 peak sun hours, using the PVWatts default losses. The inputs below are stated assumptions for a clean, unshaded panel, so replace them with your own site values and the datasheet efficiency of the unit you buy.
- Assume a 400 W panel, 5 peak sun hours, a 14 percent system loss and a 96 percent inverter efficiency.
- Multiply panel watts by peak sun hours: 400 W x 5 h = 2,000 Wh of DC energy.
- Apply the system loss: 2,000 Wh x (1 - 0.14) = 1,720 Wh.
- Apply the inverter efficiency: 1,720 Wh x 0.96 = 1,651 Wh of AC energy.
- Divide by the sun hours for the average AC power across them: 1,651 Wh / 5 h = 330 W.
| Step | Calculation | Result |
|---|---|---|
| DC energy from the panel | 400 W x 5 h | 2,000 Wh |
| After 14 percent system loss | 2,000 Wh x 0.86 | 1,720 Wh |
| After 96 percent inverter efficiency | 1,720 Wh x 0.96 | 1,651 Wh |
The two loss factors remove about 17.4 percent of the DC energy in this model. The inverter step alone removes 69 Wh of the 1,720 Wh that reach it, so the system loss budget matters more than the inverter efficiency figure.
The same model shows what panel-level conversion changes under shade. Take 10 panels of 400 W where one panel is shaded to 50 percent output, which is 200 W. This is a simplified comparison of DC power available to the inverters, before inverter efficiency.
| Layout | Calculation | DC power available |
|---|---|---|
| Micro inverter on every panel | 9 x 400 W + 1 x 200 W | 3,800 W |
| String, simplified worst case | 10 x 200 W | 2,000 W |
| Difference | 3,800 W - 2,000 W | 1,800 W |
The string row assumes the shaded panel limits the current of the whole series string. Bypass diodes inside real panels reduce that penalty, so a real string lands between 2,000 W and 3,800 W, and the exact point depends on the shade pattern.
What most guides leave out
Most guides leave out that the loss a micro inverter can help with sits mainly in the shading and mismatch lines of the system loss budget. The PVWatts manual lists the default budget as soiling 2 percent, shading 3 percent, mismatch 2 percent, wiring 2 percent, connections 0.5 percent, light-induced degradation 1.5 percent, nameplate rating 1 percent and availability 3 percent.
The eight items multiply to a loss of about 14 percent, which matches the manual's default total, rather than adding to 15. Shading and mismatch together multiply to about 4.9 percent. On the 2,000 Wh example from the previous section, that is about 100 Wh per day, a reference size for those lines rather than a ceiling, because the default shading line describes distant horizon blocking that affects every panel alike.
The other six items remain with a micro inverter system. Soiling, wiring, connections, light-induced degradation and nameplate rating still apply, and availability needs a datasheet check because the system places one unit behind every panel.
The buyer decision this exposes is to measure the shading on your own roof before paying for panel-level conversion. A site close to the 3 percent default with one panel orientation leaves little for a micro inverter to recover, while a roof with chimney, vent or neighbouring-tree shade can exceed the default and change the result.
Choosing hardware for this
Choosing hardware for a micro inverter system means matching six datasheet numbers to the panel and the grid. Each number is a limit on one side of the connection, so a mismatch shows up on paper before anything is installed.
- DC input voltage window against the panel open-circuit voltage, corrected to the lowest site temperature.
- Maximum DC input current against the panel short-circuit current.
- Rated AC output power against the panel wattage, expressed as a DC to AC ratio.
- AC output voltage and frequency against the grid where the system connects.
- Number of panel inputs per unit, which is one, two or four depending on the model.
- Monitoring and communication method, which sets how panel-level data reaches you.
The DC to AC ratio equals panel DC watts divided by the inverter rated AC watts. For a 400 W panel on a unit with an assumed 350 W AC rating, the ratio is 400 / 350 = 1.14, and the datasheet states how far the unit tolerates oversizing. Compare the grid-connection requirement of the local utility with the compliance documents the datasheet lists before you commit to a model.
Wiring decisions follow the same logic, and the guide on solar panel connection to inverter shows how panels join an inverter input. Bulk buyers can also read how to specify and assess a B2B inverter order.
LinkSolar is a China-based B2B supplier of custom & OEM solar panels, solar cells and mounting hardware. For a specification that needs a custom panel to pair with a unit, use the floating Quote Now button, and compare inverter options in the Solar Inverters collection against the six numbers above.
FAQ
How many panels does one micro inverter connect to?
One micro inverter connects to one, two or four panels, depending on the model. The datasheet states the number of inputs, and each input has its own voltage and current limits, so check them against the panel for every input.
Is a micro inverter better than a string inverter?
A micro inverter is better when shading, mixed roof orientations or panel-level monitoring matter on a site. A string inverter fits an unshaded array with one orientation and keeps fewer devices on the roof, so the shading measurement from the earlier section decides the choice.
Does a micro inverter need a battery?
A micro inverter does not need a battery to convert panel DC into AC. Grid-tied units rely on the grid signal to operate, so storage and backup power need a separate design.
What efficiency should I use for a micro inverter in calculations?
Use the efficiency stated on the datasheet of the unit you plan to buy. The 96 percent PVWatts default is a placeholder for early estimates when no datasheet is available yet.
Next step
The answer points to a selection task, so the next move is to compare inverter models against your panel and grid numbers. Before opening the collection, write down the panel wattage, its open-circuit voltage and short-circuit current, the grid voltage and frequency, and the number of panels, because those inputs decide which units fit. Browse the matching products